Mitsubishi Electric FR-A7NP Instruction Manual page 55

Profibus-dp communication function
Hide thumbs Also See for FR-A7NP:
Table of Contents

Advertisement

Name
Terminal
RH
Terminal
RM
Terminal
RL
Terminal
ECW
JOG
Terminal
AU
Terminal
CS
PZD
Command
count
SU signal
OL signal
ESW
IPF signal
Command
count
Reserved
Bit
0
High speed operation command
1
Middle-speed operation command
2
Low-speed operation command
3
Jog operation command
4
Current input selection
Selection of automatic restart after
5
instantaneous power failure
6 to 7
Not used (0 is set)
8 to 15 Used by the master to recognize the command response.
0: OFF
0
1: ON (up to frequency)
0: OFF
1
1: ON (overload alarm)
0: OFF
2
1: ON (an instantaneous power failure or undervoltage occurs)
3 to 7
Not used (0 is set)
8 to 15 Echo back of the command request.
0 to 15 Not used (0 is set, 0 is returned)
Definition
*
*
Functions assigned to terminal RH, RM,
RL, JOG, AU and CS are activated.
*
*Signal names are initial values. Using Pr.180
to Pr.182, Pr. 184 to Pr .186, you can change
output signal functions.
*
Refer to the inverter manual (applied) for
details of Pr. 180 to Pr.182, Pr. 184 to Pr. 186.
*
*
PPO TYPE SUPPORT
SPECIFICATION
49
7