Mitsubishi Electric FR-A7NP Instruction Manual page 53

Profibus-dp communication function
Hide thumbs Also See for FR-A7NP:
Table of Contents

Advertisement

Name
Fault
Power-on
inhibit
Alarm
Control
request
PZD ZSW
FU signal
RUN
signal
FWD
REW
Operation
mode
Bit
0 to 2
Not used (1 is returned)
0: Inverter normal
3
1: Inverter alarm occurrence
4 to 5
Not used (1 is returned)
6
0 is returned
Command execution normal
7
Command execution error
8
Not used (0 is returned)
9
1 is returned
0: OFF
10
1: ON (output frequency being detected) (Refer to Pr. 42 and Pr. 43 in the inverter
manual.)
0: OFF
11
1: ON (inverter running)
0: Other than forward running (during stop, reverse running)
12
1: Forward running
0: Other than reverse running (during stop, forward running)
13
1: Reverse running
0: Other than network operation mode
14
1: Network operation mode
PPO TYPE SUPPORT
SPECIFICATION
Definition
7
47