Mitsubishi Electric FR-A7NP Instruction Manual page 24

Profibus-dp communication function
Hide thumbs Also See for FR-A7NP:
Table of Contents

Advertisement

INVERTER SETTING
Pr. 340
Pr. 79
Operation Mode at Power on or Power
Setting
Setting
0 (initial
External operation mode
value)
1
PU operation mode
2
External operation mode
0
(initial
3, 4
External/PU combined operation mode
value)
6
External operation mode
X12 (MRS) signal ON..... external operation mode Switching among the external, PU, and NET operation mode is enabled
7
X12 (MRS) signal OFF ... external operation mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
1, 2
3, 4
External/PU combined operation mode
*2
6
NET operation mode
*4
X12 (MRS) signal ON .... NET operation mode
7
X12 (MRS) signal OFF ... external operation mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
10, 12
*2
3, 4
External/PU combined operation mode
6
NET operation mode
*4
7
External operation mode
*1 Operation mode can not be directly changed between the PU operation mode and network operation mode.
*2 The Pr. 340 settings "2, 12" are mainly used for communication operation using the inverter RS-485 terminal.
When a value other than "9999" (selection of automatic restart after instantaneous power failure) is set in Pr. 57 Restart coasting time, the
inverter will resume the same operation state which was in before after power has been restored from an instantaneous power failure. When
Pr.340 = "1, 10", run command from communication turns off after instantaneous power failure.
*3 Operation mode can be changed between the PU operation mode and network operation mode with
DU07) and X65 signal.
*4 Pr. 79 = "6" and Pr. 128 to Pr. 134 (PID control) are not activated simultaneously. Switchover mode and PID control are made invalid, and
the inverter performs the same operation as when "0" is set in Pr. 79.
18
Restoration
Operation Mode Switchover
Switching among the external, PU, and NET operation mode is
enabled
*1
PU operation mode fixed
Switching between the external and Net operation mode is enabled
Switching to the PU operation mode is disallowed
Operation mode switching is disallowed
Switching among the external, PU, and NET operation mode is enabled
while running.
External operation mode fixed (Forcibly switched to external
operation mode.)
Same as when Pr. 340 = "0"
Switching between the PU and NET operation mode is enabled
Same as when Pr. 340 = "0"
NET operation mode fixed
Same as when Pr. 340 = "0"
Switching between the PU and NET operation mode is enabled while running
Same as when Pr. 340 = "0"
*1
*3
*3
of the operation panel (FR-