LG LP-E5020CL Service Manual page 48

Package air conditioner
Table of Contents

Advertisement

8.3
Evacuation
(All amount of refrigerant leaked)
Vacuum pump
• Procedure
¤ Connect the vacuum pump to the center hose of charge set.
¤ŁEvacuation for approximately one hour.
- Confirm that the gauge needle has moved toward -76cmHg (vacuum of 4 mmHg or less).
¤ØClose the valve (Lo side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle
does not move (approximately 5 minutes after turning off the vacuum pump).
¤ŒDisconnect the charge hose from the vacuum pump.
- Vacuum pump oil.
If the vacuum pump oil gets dirty or depleted, replenish as needed.
Indoor unit
Lo
OPEN
CLOSE
Liquid side
3-Way
valve
Gas side
3-Way
valve
– 48 –
Outdoor unit
Open
Open