Using The Ethernet Rj-45 Interfaces - Cisco ASR 5000 Installation Manual

Hide thumbs Also See for ASR 5000:
Table of Contents

Advertisement

Using the Ethernet RJ-45 Interfaces

• Activity: This green LED shows when data is transmitted or received. The LED is illuminated when
Connect to the SFP interfaces by following the instructions below.
Step 1
To ensure full connectivity, use your thumb to firmly press the SFP transceiver module into its socket on the front panel
of the card.
Step 2
Remove the cover from the SFP module.
Step 3
Inspect and clean the connector's fiber-optic end-faces.
Step 4
Insert the fiber-optic cable from the network device into the interface and ensure that it locks in place.
Step 5
Repeat step 1 through step 5 to connect a fiber-optic cable to the other port.
Using the Ethernet RJ-45 Interfaces
The two RJ-45 interfaces are auto-sensing 10/100/1000Base-TX Ethernet interfaces. Refer to the figure and
table that follow for pinouts for the RJ-45 Ethernet ports.
Important
Important
Important
Figure 31: SPIO Ethernet RJ-45 Interface
ASR 5000 Installation Guide
90
data is passing through the interface.
To comply with GR-1089 intra-building, lightning-immunity requirements and ensure compliance with
Radiated Emissions Criteria, you must use shielded-twisted pair (STP) copper cable and ensure that it is
properly terminated at both ends.
The 1000Base-TX (RJ-45) management ports of the SPIO are suitable for connection to intra-building or
unexposed wiring or cabling only. These intra-building ports MUST NOT be metallically connected to
interfaces that connect to the outside plant (OSP) or its wiring. These interfaces are designed for use as
intra-building interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 5) and require
isolation from the exposed OSP cabling. The addition of Primary Protectors is not sufficient protection
in order to connect these interfaces metallically to OSP wiring.
Be sure to label the interface cables with their destination prior to connecting them to the SPIO card. This
will assure proper reconnection should the card need to be serviced.
Cabling the Switch Processor Input/Output Line Card

Advertisement

Table of Contents
loading

Table of Contents