Replacing The Fan Fuse (Construction Type J); Replacing The Starting Capacitor - Siemens simovert masterdrives Operating Instructions Manual

Motion control/frequency inverter (dc-ac) chassis type
Hide thumbs Also See for simovert masterdrives:
Table of Contents

Advertisement

Available languages

Available languages

08.2008
Construction type
J – L
CAUTION
9.2

Replacing the fan fuse (construction type J)

9.3

Replacing the starting capacitor

Siemens AG
6SE7087-7KN50
SIMOVERT MASTERDRIVES
The fan assembly consists of:
♦ the fan housing
♦ one or two fans
♦ the starting capacitors
The fan assembly is installed at the top in the chassis.
♦ Withdraw connector X20.
♦ Unscrew the two M8 screws of the fan assembly.
♦ In the case of type K with only one fan, you must dismantle the
support plate below the fan (2 x M8).
♦ Pull out the fan assembly towards the front (if necessary, tilt it
slightly down at the front) and lay it down securely.
The fan assembly weighs up to 38 kg, depending on its design.
♦ Undo the cable fastenings and fan connections.
♦ Take the fan support plate out of the fan assembly and remove the
fan from the support plate.
♦ Install the new fan assembly in the reverse sequence.
For type K and L: Renew contact washers for grounding.
Prior to start-up, check that the fan can run freely and check for correct
direction of air flow.
The air must be blown upwards out of the unit.
The fuses are in a fuse holder which is mounted on a DIN rail in the
bottom of the unit. The fuse holder has to be opened to replace the
fuses.
The starting capacitor is
• next to the fan connection (types E - G)
• on or inside the fan assembly (type J – L).
♦ Withdraw the plug connections on the starting capacitor.
♦ Unscrew the starting capacitor.
♦ Install the new starting capacitor in reverse sequence (4.5 Nm).