Siemens SITRANS F M TRANSMAG 2 Operating Instructions Manual page 55

Electromagnetic flowmeters
Table of Contents

Advertisement

Digital output 1 (Menu item 4.2)
You have the following setting options in this menu:
● Function, menu item 4.2.1
● Signal type, menu item 4.2.2
You can generate signals with positive and negative logic (positive and negative pulses).
The figure below illustrates the setting options.
SITRANS F M TRANSMAG 2
Operating Instructions, 11/2009, A5E00102775-07
You can configure digital output 1 as a pulse, frequency, alarm or status output
When "Split value active" is selected, the output is active when the current level of the
flow value is within the lower subdomain 0 to
"Split value"; the output current is then scaled to the 0 to "Split value" range. If the flow
value exceeds this subdomain, the output current is scaled to the 0 to URV range.
You can configure different signal types for the output signal of digital output 1:
– Active:
The device-internal voltage is used (+24 V).
– Passive:
External supply required.
Active
Passive
Counter
External supply max. DC 30 V
Figure 7-6
Active and passive signals
7.5 Function Group Device Outputs
Functions
53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents