GE Multilin MM300 Quick Start Manual page 49

Motor management system
Hide thumbs Also See for Multilin MM300:
Table of Contents

Advertisement

UPGRADING RELAY FIRMWARE
40
If there is no RS232 port on your PC:
1.1.
If you are using the MM300 Graphical Control Panel (GCP) or Hand Held
Device (HHD), connect the USB port on the front of the MM300 relay, to the USB
port on the local PC, using a USB 2.0 type A to mini B cable. This configuration
(1) is shown below.
1.2.
If you are using the Basic Control Panel (BCP), and your PC has an RS232 port,
disconnect the existing RJ45 cable from the side of the base unit (labelled
"RS485 to Control Panel"), and connect an RS232-to-RJ45 cable from the PC to
that same RJ45 port on the side of the base unit. This configuration (2) is shown
below.
1.3.
If you are using no control panel, and your PC has an RS232 port, connect an
RS232-to-RJ45 cable from the PC to the RJ45 port on the side of the base unit
(labelled "RS485 to Control Panel"). This configuration (2) is shown below.
Note 1: If your PC does not have an RS232 port, you will have to use a USB-to-serial
converter cable (p/n 0100-0001), available at the GE Online Store (http://
www.gegridsolutions.com). This configuration (3) is shown below.
Note 2: If the unit does not have Graphical Control Panel (GCP), you will have to use a
RS232 to RJ45 custom cable (p/n 0804-0180), available at the GE Online Store (http://
www.gegridsolutions.com).
Note 3: If you use a USB-to-serial converter cable (see Note 1 above), the effective
COM port for this configuration, will be COM10 as shown below.
(1)
PSU
USB
Port
(2)
PSU
USB
Port
(3)
RS232-to-RJ45 cable (COM10)
USB (Mini-B)-to-USB (Type-A) cable
RS232-to-RJ45 cable
USB-to-Serial converter cable
MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE