Choose Location; Choose Mounting Position - Honeywell F50F Installation Instructions Manual

Electronic air cleaner
Hide thumbs Also See for F50F:
Table of Contents

Advertisement

F50F DUCT MOUNTED ELECTRONIC AIR CLEANER
terminals. The W8600F air cleaner monitor can be mounted
in the living area or in the furnace room. It should be located
in a convenient location to observe the display.
NOTE: The W8600F is not available in Europe.

Choose Location

Choose a location that is readily accessible for regular
inspection and cleaning. Allow at least 13 in. (330 mm) in
front of the access door for removing the prefilter and
electronic cell. Allow enough room above the power supply
so it can be serviced without removing pipes, ducts, or
other heating system components.
The air cleaner must be installed where the temperature
does not exceed 40°F to 125°F (4°C to 52°C).

Choose Mounting Position

WARNING
Heavy Equipment Hazard.
Can cause injury or equipment damage.
Do not mount the air cleaner with the access door
facing down. If the access door faces down, the
latch may not hold, and the cell and prefilter can
fall unexpectedly. Also, nothing holds the cell and
prefilter in place when the access door is opened.
A
E
69-1150—2
B
F
Fig. 1. Mounting positions with a variety of furnace installations.
The air cleaner can be mounted in any position except with
the access door facing down. Following is a list of air
cleaner mounting positions for a variety of furnace
installations.
NOTE: At least 13 in. (330 mm) clearance is required
between the access door and any obstructions
for cell and prefilter maintenance.
— Upflow "Highboy" furnace : Side installation; air
cleaner is mounted vertically where return enters side
inlet of furnace. See Fig. 1A.
— Downflow "Highboy" furnace: Installation beneath
furnace (air cleaner cabinet can easily support weight
of furnace and air conditioner coil). Air cleaner is
mounted horizontally where return enters from below.
See Fig. 1B.
— Upflow "Highboy" furnace: Closet installation. Air
cleaner is mounted vertically on furnace between
furnace and louvered return air opening in closet door.
See Fig. 1C.
— "Lowboy" furnace: Air cleaner is mounted horizontally
in return plenum just above furnace, opposite supply
plenum. See Fig. 1D.
— Downflow "Counterflow" furnace: Air cleaner is
mounted horizontally in return duct or plenum just
above furnace. See Fig. 1E.
— High capacity system: Two or more air cleaners can
be used together. See Fig. 1F.
— Electric furnace or heat pump: Single cell air cleaner
is mounted with access door on top. See Fig. 1G.
— Horizontal furnace: Air cleaner is mounted vertically
where return enters. See Fig. 1H.
C
G
2
D
H
M11973