Room Ventilation - Beko HIDG 95225 SX AU User Manual

Hob gas 5 b
Table of Contents

Advertisement

STANDARD
COUNTER TOP
50 - 60 mm.
THICKER
COUNTER TOP
Requirement 1 Overhead clearances A)
Range hoods and exhaust fans shall be
installed in accordance with the
manufacturer's relevant instructions.
However, in no case shall the clearance
between the highest part of the hob of the
gas cooking appliance and a range hood be
less than 600 mm or, for an overhead
exhaust fan, 750 mm.
Requirement 2 Side Measurements B, &
C) Where B, measured from the periphery of
the nearest burner to any vertical
combustible surface, or vertical combustible
surface covered with toughened glass or
sheet metal, is less than 200 mm, the
surface shall be protected to a height C of
not less than 150 mm above the hob for the
full dimension (width or depth) of the cooking
surface area. Where the gas cooking
appliance is fitted with a 'splashback',
protection of the rear wall is not required.
Page 12
HOB
30 - 40 mm.
SECURING BRACKET
AND SCREW
HOB
Top thickness
SECURING BRACKET
AND SCREW
Baffle installation
Hose connection
Flexible hose assembly (if used) must
comply with AS/NZS 1869 Class B or D, be
of appropriate internal diameter, be kept as
short as possible (not to exceed 1.2 meters),
must not be kinked or in contact with any hot
surface. The supply connection point shall
be accessible with the appliance installed.

Room ventilation

All rooms require a window that can be
opened, or equivalent, and some rooms will
require a permanent vent in addition.
Air for combustion is drawn from the room
and the exhaust gases are emitted directly
into the room, therefore good room
ventilation is essential for the safe operation
of your appliance. If there is no window or
door available for room ventilation, extra
ventilation must be installed.
The appliance may be located in a kitchen,
kitchen/diner or a bed-sitting room, but not in
a room containing a bath or shower. The
appliance must not be installed in a bed-
sitting room of less than 20m
this appliance in a room below ground level
unless it is open to ground level on at least
one side.
Room size
3
Smaller than 5 m
3
3
5 m
to 10 m
Greater than 10 m
In the cellar or basement
3
. Do not install
Ventilation
opening
min. 100 cm
min. 50 cm
3
not required
min. 65 cm
2
2
2