Project Planning; Compatibility; Range Of Application; Restrictions - Siemens fdsb291 Technical Manual

Bass sounder
Hide thumbs Also See for fdsb291:
Table of Contents

Advertisement

Project planning

4
Project planning
4.1

Compatibility

4.2

Range of application

4.3

Restrictions

20
Building Technologies
Fire Safety & Security Products
Please always take the country-specific provisions and the alarm organization for
project planning into account. In addition, the connection factors stated in the
specifications must also be taken into account.
See also
 Technical data [ 30]
Compatible with control panels that support the FDnet detector line.
For details see 'List of compatibility'.
Living rooms and lounges
Hotel rooms
Sick rooms
No direct interface to detector exchanger and tester FDUD292 and to intelligent
detector tester FDUD293. A function test of the sounder base FDSB291 with a
detector exchanger and tester FDUD292 or an intelligent detector tester
FDUD293 is only possible if a point detector is inserted in the sounder base
FDSB291. Communication between test device and sounder base is via the
point detector.
Not compatible with detector heating unit FDBH291
Cannot be synchronized with the alarm sounder FDS221 (only for product
version <30)
Cannot be installed in wet areas
Cannot be operated on a collective detector line
WARNING
Operating the sounder base on a collective detector line prevents alarms and
faults from being recorded and processed.
Fire may spread unhindered.
Do not use the sounder base FDSB291 on a collective detector line.
007025_i_en_--
07.05.2010