STANDARD PARTS
The following installation parts are furnished.
Use them as required.
INDOOR UNIT ACCESSORIES
SS
QQ R R
CC P P
AA B B
  
 @ @
Description
Drain hose insulation
VT wire
Coupler heat insulator
(large)
Coupler heat insulator
(small)
Nylon fastener
Special nut A
(large flange)
Special nut B
(small flange)
Installation template
Auxiliary pipe assembly
Indoor capillary tube
BR sheet
Q'ty
Application
Adhesive type
70 x 230
1
For fixing the drain
1
hose L 280 mm
For indoor side
pipe joint
(large pipe)
2
For indoor side
pipe joint
1
(small pipe)
Large
For fixing the
4
coupler heat
insulator
Small
4
For installing
indoor unit
4
For installing
indoor unit
4
For positioning
the indoor unit
1
For connecting
the piping
1
(This part is
enclosed with the
1
30,000 and 36,000
BTU/h versions.)
65 x 130 x T5
(This part is
2
enclosed with the
30,000 and 36,000
BTU/h versions.)

CONNECTION PIPE REQUIREMENT

45,000 / 36,000
BTU/h class
30,000
BTU/h class
Use 0.7 mm to 1.2 mm thick pipe.
Use pipe with water-resistant heat insulation.
Use pipe that can withstand a pressure of 3,040 kPa.

ELECTRICAL REQUIREMENT

Connection
cord (mm
)
2
Always use H07RN-F or equivalent as the connec-
tion cord.
Install the disconnection device with a contact gap
of at least 3 mm nearby the units. (Both indoor unit
and outdoor unit)
– 3 –
Table 1
Diameter
Small
Large
9.53 mm
19.05 mm
9.53 mm
15.88 mm
Table 2
MAX
2.5
MIN
1.5