10.1. Power supply wiring

Power supply cords of appliances shall not be lighter than design 245 IEC 57
or 227 IEC 57.
A switch with at least 3 mm contact separation in each pole shall be provided
by the Air conditioner installation.
ELECTRICAL WORK
1. Electrical characteristics
Model
PWFY-P100VM-E-BU
Model
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
2. Power cable specifications
Minimum wire thickness (mm
Model
Main cable
PWFY-P100VM-E-BU
2.5
Model
Total
PWFY-P100VM-E-AU
operating
PWFY-P200VM-E-AU
current
[Fig. 10.1.1] (P. 4)
A Breaker for current leakage
B Local switch or breakers for wiring
C PWFY-P100VM-E-BU
D PWFY-P100/200VM-E-AU
E Pull box
Caution:
Do not use anything other than the correct capacity breaker and fuse. Us-
ing fuse, wire or copper wire with too large capacity may cause a risk of
malfunction or fire.
10.2. Connecting remote controller, indoor
and outdoor transmission cables
(Remote contoroller is optionally available.)
Connect unit TB5 and outdoor unit TB3. (Non-polarized 2-wire (shield))
The "S" on unit TB5 is a shielding wire connection. For specifications about
the connecting cables, refer to the outdoor unit installation manual.
Install a remote controller following the manual supplied with the remote con-
troller.
Connect the "1" and "2" on unit TB15 to a MA remote controller. (Non-polar-
ized 2-wire)
[Fig. 10.2.1] (P.4) MA Remote controller
DC 10 to 13 V between 1 and 2 (MA remote controller)
[Fig. 10.2.2] (P.4) MA Remote controller
The MA remote controller cannot be used at the same time or interchange-
ably.
A Non-polarized
C MA remote Controller
E TB2 (Power supply wiring)
Note:
Ensure that the wiring is not pinched when fitting the terminal box cover.
Pinching the wiring may cut it.
Caution:
Use wire with supplemental insulation.
Input to TB142A, TB142B, and TB142C should not carry voltage.
Cables from equipment connected to external input/output should have sup-
plemental insulation.
Use a single multiple-core cable for external input/output to allow for connec-
tion to the PG screw.
Caution:
Wire the power supply so that no tension is imparted. Otherwise discon-
nection, heating or fire result.
Power supply
Hz
Volts
Voltage range
Max. 264 V
50/60
220-230-240 V
Min. 198 V
Hz
Volts
50/60
220-230-240 V
2
Breaker for
)
current leakage
branch
Ground
30 A 30 mA 0.1 sec or less
-
2.5
Minimum wire thickness (mm
Main cable
branch
16 A or less
1.5
1.5
25 A or less
2.5
2.5
32 A or less
4.0
4.0
B TB15 (MA remote controller cables)
D TB5 (Transmission cables)
MCA (A)
Output (kW)
15.71
1.0
Power supply
Voltage range
Max. 264 V
Min. 198 V
Local swich (A)
capacity
fuse
25
25
2
)
Breaker for
current leakage
Ground
1.5
20 A 30 mA 0.1 sec. or less
2.5
30 A 30 mA 0.1 sec. or less
4.0
40 A 30 mA 0.1 sec. or less

10.3. External input/output function

Preset temperature input (external analog input: 4mA-20mA)
External input is input through CN421, CN422 on the circuit board. (Fig. 10.3.1)
Use the supplied connector.
If no temperature settings are made via the MA remote controller, the temperature
changes with the current.
Refer to the instructions manual that came with the MA remote controller for how
to make the settings.
4 mA → 10 °C
External output terminal
External output terminal (refer to Fig. 10.3.2) is ineffective when the circuit is open.
Refer to Table 10.3.2 for information about each contact.
The current in the circuit to be connected to the external output terminal must be
0.6A or less.
Table10.3.2
OUT1
OUT2
OUT3
OUT4
External input terminal
The piping length must be within 100 m.
External input terminal (refer to Fig. 10.3.3) is ineffective when the circuit is open.
Refer to Table 10.3.3 through Table 10.3.5 for information about each contact.
Only the "pump interlock" function is ineffective when the circuit is short-circuited.
Connect a relay circuit to the external output terminal as shown in Fig. 7.4.1.
The specifications of the relay circuit to be connected must meet the following
conditions.
Contact rating voltage
Contact rating current
Minimum applicable load
Table10.3.3
TB142A
IN1
Table10.3.4
TB142B
IN3
IN4
Table10.3.5
TB142C
COM+
IN5*1
IN6*2
IN7*3
*1 PWFY-P100VM-E-BU
PWFY-P100/200VM-E-AU
*2 Effective when SW 4-3 is set to ON.
*3 Effective when SW 4-4 is set to ON.
Compressor
SC (A)
1.25
11.63-11.12-10.66
RLA (A)
Cooling
MCA (A)
0.068-0.065-0.063
0.085
Breaker for wiring (NFB) (A)
30
Local swich (A)
Breaker for wiring (NFB) (A)
capacity
fuse
16
16
25
25
32
32
20 mA → 70 °C
Operation ON/OFF
Defrost
Compressor
Error signal
DC15V
=
0.1A
=
1mA at DC
=
Pump interlock
Connection demand
Operation ON/OFF
Common
Hot Water/Heating
Heating ECO
Anti-freeze
Hot Water
Heating
RLA (A)
Heating
Heating
20
30
40
11