Power Factor Correction
The power supply contains an active PFC (Power Factor Correction) circuit to conform to the
EMC guidelines.
Uninterruptible AC power systems (UPS) must supply a sinusoidal output voltage in the
normal and buffered mode when used with SIMATIC PCs with an active PFC.
UPS characteristics are described and classified in the standards EN 50091-3 and IEC
62040-3. Devices with sinusoidal output voltage in the normal and buffered mode are
identified with the classification "VFI-SS-...." or "VI-SS-....".
Notice
Risk of damage
Operation of the device on a non-sinusoidal mains voltage can cause damage to the power
supply unit.
Country-specific Connection Information
For the USA and Canada
For the United States and Canada, a CSA or UL-listed power cord must be used. The
connector must be compliant with NEMA 5-15.
Country-specific power cables are available as accessories.
• 120 V supply voltage
• 230 V AC power supply
For countries other than the USA and Canada
• Please observe the country-specific supply voltage
Connecting the power supply
Steps for connecting the device to the 100 - 240 V AC power supply
1
2

Power consumption

Depending on the size of the display and taking into account 15 W per PCI slot, the power
consumption for devices with 12" and 15" operator control units is max. 140 W, and with 19"
operator control units it is max. 163 W.
SIMATIC Panel PC 677
Operating Instructions (Compact), Edition 07/2006, A5E00877730-01
Use a flexible power cord with UL approval and with CSA label, and with the following
features: Type SJT with three leads, min. 18 AWG conductor cross-section, max. 4.5 m in
length and parallel ground contact connector 15 A, min. 125 V
To be used is a flexible power cord approved to UL and with CSA label, and which has
the following features: Type SJT with three leads, min. 18 AWG conductor cross-section,
max. 4.5 m long and tandem ground contact connector 15 A, min. 250 V
This device is equipped with a safety-tested power cord which may only be connected to
ground contact power outlet. If you choose not to use this cable, you must use a flexible
cable of the following type: Min 18 AWG conductor cross-section and 15-A / 250-V
shockproof connector. The cable set must be compliant with the safety regulations and
stipulated IDs of the country where the system is to be installed.
Switch off the AC power source
Connect the power supply using the connector
Operating instructions (compact)
1.5 Connecting
1-15