Toshiba T300MVi MEDIUM VOLTAGE Instruction Manual page 49

Hide thumbs Also See for T300MVi MEDIUM VOLTAGE:
Table of Contents

Advertisement

QSTOP
Quick stop command
R-TEN
Reverse tension command
SEL_DI
Start/Stop/Reference/direction select
SPA0
Spare 0
SPA1
Spare 1
SPA2
Spare 2
SPA3
Spare 3
SPA4
Spare 4
SP_UP_DI
Raise speed reference
SP_DN_DI
Lower speed reference
START0_DI
Start command for three wire control 0
START1_DI
Start command for three wire control 1
STOP0_DI
Stop command for three wire control 0
STOP1_DI
Stop command for three wire control 1
ST_CLUTCH
Torque control selection
UVS
Operation interlock
rd
3S
3
jogging speed command
nd
2S
2
logging speed command
"**" The function of many operation signals can be reversed via settings for SGN_DI1-8 or SGN_DI_EX4 if needed.
1:Quick stop, 0:Normal stop
1:Reverse tension control on,
0:Forward tension control on
0:Use EXT0,START0,STOP0,SP_REF_AIN1,DIR0_DI
1:Use EXT1,START1,STOP1,SP_REF_AIN2,DIR1_DI
Spare 0 (For future use)
Spare 1
Spare 2
Spare 3
Spare 4
0:no change, 1:Raise speed reference
(Operates only when keypad is in remote mode. Use in
conjunction with CR_RATE_MRH)
0:No change, 1:Lower speed reference
(Operates only when keypad is in remote mode. Use in
conjunction with CR_RATE_MRH)
0:No start, 1:Start
(Must be momentary. Refer to SEL_DI)
0:No stop, 1:Stop
(Refer to SEL_DI)
1:Tension control,
0: Speed control (when torque control is selected)
1:Interlock released, 0: Interlocked
(3S, 2S)=(0,0) :Jog speed 1 used
(3S, 2S)=(0,1) :Jog speed 2 used
(3S, 2S)=(1,0) :Jog speed 3 used
(3S, 2S)=(1,1) :No jog speed used
- 28