General Cubicle Structure

The configuration and dimensions of the equipment are described below.

Cubicle Structure and Dimensions

The equipment is made up of one or more cabinets containing the transformer, incoming terminals,
converter section, and the inverter section. All components can all be accessed from the front.
This outline is for the standard Frame 1 model. For details of this and other ratings, see the outline
drawing of each product.
P O W E R
IS O L A T IO N
S W IT C H
O
N
O
F
F
T R A N S F O R M E R / C O N V E R T E R C U B IC L E
Dimensional Outline of 4160V- Frame 1 Cubicle
(See the following page for dimensions)
General structure
1) All cubicles have a structure that allows maintenance from the front. Rear maintenance access is
not required. The cubicles may be placed within 1" of the rear wall.
2) Provide a maintenance space of at least 72 inches (1829 mm) in front of the cubicles.
3) Provide a clearance of at least 24 inches (610 mm) above the exhaust fans.
4) The following are not included in the dimensions on the next page:
a) Handle projections
b) Door mounted device projections
c) Fastener projections
IN V E R T E R / C O N T R O L
W ID T H
- 21
H E IG H T
D E P T H