Security Function

1.1 Overview of Security Function

1.1.1 Precautions on Using Security Function

 Security information set for each function can be cleared using the tool software, however,
performing the clearing operation also deletes project data. Fully confirm before determining
the operations of each security function.
 Although the encryption function encrypts programs to make them unreadable, it cannot
protect projects from being read or rewritten. Use the password protection function in
combination as necessary.

1.1.2 Type of Security Functions

 Password function (1)
 This is a function to set a password for project data downloaded to the PLC for preventing
data from being read and written. Using this function prevents unnecessary rewrting or leak
of know-how.
 The password is valid for configuration data, ladder programs and comments.
 Operation memories can be read or written even when a password has been set.
 A project for which a password has been set is saved as a password-protected file even
when it is saved on a PC. (Available in FPWIN GR7 Ver.1.3 or later)
Item
No. of registerable passwords
No. of characters
Open and close for each
communication route
Limit on number of failed open
request
Status when power is on
(Note) The number one password is set with administrator privileges.
FP7 CPU
1-2
Specifications
16 (Settable as administrator or users) (Note)
8 to 16 characters
Only connected port is allowed to access.
Access is blocked when opening operation failed three times. It is
recovered when the power turns on again.
All passwords are closed when the power turns on.