Target Pressure Adjusting - LG multi v Installation Manual

Hide thumbs Also See for multi v:
Table of Contents

Advertisement

Target pressure adjusting

mode setting method
Setting
mode
"Heat"
op1
Increase capacity
op2
Decrease power consumption
op3
Decrease power consumption Decrease power consumption +2.5°C(36.5°F) -4°C(24.8°F)
op4
Decrease power consumption Decrease power consumption -4.5°C(23.9°F)
!
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn8" Push the '●' button
Select the Option using '▶', '◀' Button :
"HEAT" , "COOL" Push the '●' button
Select the Option using '▶', '◀' Button :
"op1" ~ "op4" Push the '●' button
Target pressure is set
Purpose
"Cool"
Increase capacity
Increase capacity
TEST RUN
Condensing
Evaporating
temperature
temperature
variation
variation
-3°C(26.6°F)
+2°C(35.6°F)
-1.5°C(29.3°F)
-2°C(28.4°F)
-6°C(21.2°F)