Download Print this page

Setting The Indoor Unit Address - LG PACP4B000 Installation & User Manual

Hide thumbs

Advertisement

10
Installing ACP IV

Setting the indoor unit address

By considering the entire installation configuration connecting to one ACP IV, set the address to
each indoor unit not to be overlapped. 00~FF in hexadecimal can be set to the indoor unit address.
However, in case of I/O module, address 00 should not be set because address 00 is used as
Broadcast in MODBUS communication.
NOTES
Assigning indoor and outdoor unit number
If the outdoor unit product is Multi V, it is
recommended to assign the address by setting
the first digit of the address as the number of the
outdoor unit, and classifying the second digit as the
number or the indoor unit, for easy composition and
classification of the system.
Here is an example of configuring ACP IV and the device.

Advertisement