Binary Value
Object Name
Object ID
Binary Value #14
Fault Reset
(BV14)
Binary Value #18
Preset Spd 1
(BV18)
Binary Value #19
Preset Spd 2
(BV19)
Binary Value #20
Preset Spd 3
(BV20)
Binary Value #21
Freq Ovrd
(BV21)
Binary Value #22
Cmd Ovrd
(BV22)
R = Read-only; C = Commandable
Analog Input
Analog Input
Terminal
Object ID
Analog Input #0
RR
(AI0)
Analog Input #1
V/I
(AI1)
Analog Input #2
RX
(AI2)
Analog Input #3
AI1*
(AI3)
Analog Input #4
AI2*
(AI4)
* The ETB004Z expansion I/O card is required to use this input.
R = Read-only
Q9 Plus ASD Quick Start Guide
®
Table 5. BACnet
Binary Values. (Continued)
Description
Commands the drive to reset a fault
Commands the Preset Speed 1 operation
Commands the Preset Speed 2 operation
Commands the Preset Speed 3 operation
Overrides the Frequency Mode 1 (F004) selection
Overrides the Command Mode (F003) selection
®
Table 6. BACnet
Object Name
RR Level
Input level of the RR analog input
V/I Level
Input level of the V/I analog input
RX Level
Input level of the RX analog input
AI1 Level
Input level of the AI1 analog input
AI2 Level
Input level of the AI2 analog input
Analog Inputs.
Description
Status
Access
Reset/No
C
SP1/None
C
SP2/None
C
SP3/None
C
Enabled/Off
C
Enabled/Off
C
Value
Access
Percent (%)
R
of full scale
Percent (%)
R
of full scale
Percent (%)
R
of full scale
Percent (%)
R
of full scale
Percent (%)
R
of full scale
69