Inlet Protection Mag 3100; Cathodic Protected Piping - Siemens MAG 1100 Handbook

Electromagnetic flowmeters
Table of Contents

Advertisement

SITRANS F M MAGFLO
MAG 3100
(PTFE liner)
5.2

Inlet protection MAG 3100

5.3

Cathodic protected piping

38
5. Installation of sensor
Potential equalization, electrically conductive
pipe
Type of earthing flange depending on liner
material
DKFD.PS.027.W3.02
Electrically conductive piping
Use an earth straps on one side.
Non-conductive piping
Use an earthing flange. Place the flange between
flowmeter and the adjacent pipe flange.
Selection of earthing flange depends on the
medium, liner material and application, see
figure.
Liner
material
earthing flange
PTFE
With abrasive liquids, flowmeter inlet protection
may be necessary. Here type C and E earthing
flanges are used.
Type C (for all liners except PTFE) is clamped
between the flanges.
Type E (for PTFE liner only) is fitted to the
flange.
When using an earthing flange, gaskets must
always be used between the adjacent pipe
flange and the earthing flange.
Special attention must be given to systems with
cathodic protection.
Compact installation:
The signal converter must be supplied through
an isolation transformer. The terminal "PE" must
never be connected.
Remote installation:
The screen must only be connected at the
sensor end via a 1.5 µF condensator. The
screen must never be connected at both ends.
Isolated sensor:
If above mentioned connections are unaccept-
able, the sensor must be isolated from the pipe
work.
Suitable
Type E