Menu
6.7 Know-how Protection
5.
6.
7.
8.
9.
10.
86
Parameter p7764 is displayed. Press "OK" to edit the
parameter.
Indices "0" of P7764 is highlighted and shows that it
already has the value 7766, which is the password entry
parameter. This parameter must not be removed from
the exception list.
Scroll to the next Indices and press "OK"
Input the parameter number to be added to the
exception list. For example, 1120 for the ramp-up time
parameter.
Press "OK" after the final digit has been set.
The screen will return to the indices list of p7764 and
show the new value for the indices. In this example
p7764 [1] has a value of 1120.
Repeat steps 7 and 8 until all the excluded parameters
have been entered.
When the exception list is completed, use a long press
of the "ESC" key will return the IOP to the status screen.
Operating Instructions, 03/2013, FW V1.4, A5E00110011A4 AB