Example Wizard; Basic Commissioning With Iop - Siemens Sinamics G120 Operating Instructions Manual

Radio wall transmitters intelligent operator panel
Hide thumbs Also See for Sinamics G120:
Table of Contents

Advertisement

4.1

Example wizard

Overview of wizards
The following example of how wizards work on the IOP are purely for demonstration purpose
only. It should be understood that the screens, questions and steps for each wizard are
dependent on the following influences:
● The firmware version of the IOP in use.
● The firmware version of the Control Unit to which the IOP is fitted.
● The type of Control Unit to which the IOP is fitted - not all Control Units have the same
4.1.1

Basic commissioning with IOP

Basic commissioning wizard
Note
Software limitations
The Basic Commissioning wizard detailed below is for Control Units with version 4.3
software or earlier.
Intelligent Operator Panel (IOP)
Operating Instructions, 03/2013, FW V1.4, A5E00110011A4 AB
functionality and this will change the structure of the IOP menus including the type and
number of wizards that will be offered to the user.
CAUTION
Before commissioning an application
Prior to using the a wizard, it is essential that the user's Control Unit and Power Module
have been installed and wired correctly, in accordance with the requirements of the
user's application. This is extremely important in the case of commissioning safety-
integrated applications. All inputs and outputs must be defined and configured before
any commissioning can take place, including the observation and adherence of all local,
national and international safety regulations required for the user's application and all
devices utilitzed by the user's application.
Wizards
4.1 Example wizard
29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120cSinamics iop

Table of Contents