Applicable Cables And The Wiring Length - Mitsubishi Electric FR-A800 Instruction Manual

Hide thumbs Also See for FR-A800:
Table of Contents

Advertisement

Main circuit terminals
2.5.4

Applicable cables and the wiring length

Select a recommended cable size to ensure that the voltage drop will be 2% or less.
If the wiring distance is long between the inverter and motor, the voltage drop in the main circuit wires will cause the motor
torque to decrease especially at a low speed.
The following table indicates a selection example for the wiring length of 20 m.
• 400 V class (440 V input power supply (with 150% rated current for one minute))
Applicable
Terminal
Tightening
inverter
screw
model
size

FR-A846-[ ]
00023(0.4K) to
M4
1.5
00126(3.7K)
00170(5.5K)
M4
1.5
00250(7.5K)
M6
4.4
00310(11K)
M6
4.4
00380(15K)
M6
4.4
00470(18.5K) M6
4.4
00620(22K)
M6
4.4
00770(30K)
M6
4.4
00930(37K)
M8
7.8
01160(45K)
M8
7.8
01800(55K)
M10
14.7
02160(75K)
M10
14.7
02600(90K)
M10
14.7
03250(110K)
M10
14.7
03610(132K)
M10
14.7

For the FR-A846-01800(55K) or lower, it is the gauge of a cable with the continuous maximum permissible temperature of 75°C (HIV cable (600
V grade heat-resistant PVC insulated wire), etc.). It assumes a surrounding air temperature of 50°C or lower and the wiring distance of 20 m or
shorter.
For the FR-A846-02160(75K) or higher, it is the gauge of the cable with the continuous maximum permissible temperature of 90°C or higher.
(LMFC (heat resistant flexible cross-linked polyethylene insulated cable), etc.). It assumes a surrounding air temperature of 50°C or lower.

For the FR-A846-01160(45K) or lower, it is the gauge of a cable with the continuous maximum permissible temperature of 75°C (THHW cable).
It assumes a surrounding air temperature of 40°C or lower and the wiring distance of 20 m or shorter.
For the FR-A846-01800(55K) or higher, it is the gauge of a cable with the continuous maximum permissible temperature of 90°C (THHN cable).
It assumes a surrounding air temperature of 40°C or lower. (Selection example for use mainly in the United States.)

For the FR-A846-01160(45K) or lower, it is the gauge of a cable with the continuous maximum permissible temperature of 70°C (PVC cable). It
assumes a surrounding air temperature of 40°C or lower and the wiring distance of 20 m or shorter.
For the FR-A846-01800(55K) or higher, it is the gauge of a cable with the continuous maximum permissible temperature of 90°C (XLPE cable).
It assumes a surrounding air temperature of 40°C or lower. (Selection example for use mainly in Europe.)

The terminal screw size indicates the size of terminal screw for R/L1, S/L2, T/L3, U, V, W, P/+, N/-, P1, and a screw for earthing (grounding).
The line voltage drop can be calculated by the following formula:
Line voltage drop [V]=
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
NOTE
• Tighten the terminal screw to the specified torque.
A screw that has been tightened too loosely can cause a short circuit or malfunction.
A screw that has been tightened too tightly can cause a short circuit or malfunction due to the unit breakage.
• Use crimping terminals with insulation sleeves to wire the power supply and motor.
28
INSTALLATION AND WIRING
Crimping
terminal
torque
R/L1,
R/L1,
U, V,
N·m
S/L2,
S/L2,
W
T/L3
T/L3
2-4
2-4
2
2-4
2-4
2
5.5-6
5.5-6
3.5
5.5-6
5.5-6
5.5
8-6
8-6
8
14-6
8-6
14
14-6
14-6
14
22-6
22-6
22
22-8
22-8
22
38-8
38-8
38
60-10 60-10 60
60-10 60-10 60
60-10 60-10 60
80-10 80-10 80
100-10 100-10 100
× wire resistance[mΩ/m] × wiring distance[m] × current[A]
2
HIV cables, etc. (mm
)

Earthing
U, V,
P/+,
(grounding)
W
P1
cable
2
2
2
2
3.5
3.5
3.5
3.5
3.5
5.5
5.5
5.5
8
8
5.5
8
14
8
14
22
14
22
22
14
22
22
14
38
38
22
60
60
22
60
60
22
80
80
22
60
80
38
100
100
38
1000
Cable gauge
AWG/MCM

PVC cables, etc. (mm
R/L1,
R/L1,
U, V,
S/L2,
S/L2,
W
T/L3
T/L3
14
14
2.5
2.5
12
14
2.5
2.5
12
12
4
4
10
10
6
6
8
8
10
10
6
8
16
10
6
6
16
16
4
4
25
25
4
4
25
25
1
2
50
50
1/0
1/0
50
50
1/0
1/0
50
50
3/0
3/0
50
50
3/0
3/0
70
70
4/0
4/0
95
95
2
)

Earthing
U, V,
(grounding)
W
cable
2.5
4
4
10
10
16
16
16
16
25
25
25
25
35
50

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents