Right click on a channel to open the
Output Configuration Window.
The PS has supervision controls to
protect itself and loaded circuits.
The user has complete control of PS
parameters.
The channel will not
operate properly or even turn on
without setting up the parameters
correctly.
Fig. 4.9: U0 Output Configuration
Supervision:
Decide what is the permissible range of Sense Voltage[V]? Enter those values here,
Eg 3.130V and 3.470V respectively
Enter the maximum Terminal Voltage[V] permitted. The Terminal Voltage, will be higher than
sense voltage as discussed previously. Eg 4.50V
Enter the max, Current, Eg 115A or less.
Fig. 4.10: Supervision Parameters