Makita G SERIES Instructions For Use Manual page 20

Table of Contents

Advertisement

[ CAUTION ]
The duplex 120V receptacle is protected by a GFCI (Ground Fault Circuit
Interrupter). GFCI shuts off the output current from the duplex 120V
receptacle when a ground fault occurs in the generator or the appliance.
Please note that other receptacles are not protected by GFCI.
GFCI RECEPTACLE
After starting the engine, check the GFCI for proper functioning by the following
test procedure.
Push blue TEST button, The red RESET button will pop out exposing the word
TRIP. Power is now off at the outlets protected by the GFCI, indicating that the
device is functioning properly.
If TRIP dose not appear when testing, do not use the generator.
Call a qualified electrician.
To restore power, push RESET button.
WARNING
If the RESET button pops out during operation, stop the generator
immediately and call a qualified electrician for checking generator and
the appliances.
(5) Turn the AC circuit breaker ON, and
check if the pilot lamp lights up.
(6) Turn on the switch of the appliance.
− 14−
ON
OFF
L A M P
P I L O T

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G12000r

Table of Contents