• COOLING ONLY(LT-D5480CL, LT-D5480CA)
INDOOR UNIT
CAPILLARY TUBE
HEAT
EXCHANGER
(CONDENSER)
Pipe Size
Capacity
GAS LIQUID
54K
3/4"
1/2"
• Rated performance for refrigerant line length of: 7.5m
• If 54K Capacity is installed at a distance of 15m, 450g of refrigerant
should be added ....................................................(15-7.5) x 60g
LIQUID SIDE
GAS SIDE
Elevation (m)
Length (m)
Max.
Max.
Rated
Rated
5
30
7.5
50
OUTDOOR UNIT
COMPRESSOR
* Additional
refrigerant
(g/m)
60
–9–
HEAT
EXCHANGER
(CONDENSER)