Trouble Shooting - Haier AU182XFERA Installation Manual

X-multi inverter
Hide thumbs Also See for AU182XFERA:
Table of Contents

Advertisement

Available languages

Available languages

Trouble shooting

FAILURE
STATE OF
CODE
LED 5-4-3-2-1
1
2
3
4
5
6
9
10
11
12
13
14
15
16
17
21
23
24
25
26
27
28
29
30
31
Take off the plastic cover on the right side of the unit, you can find the LEDs near the communication
terminal. Symbol means the LED is ON, and symbol means the LED is OFF.
TROUBLE
SHOOTING
Faulty defrost sensor Te
Faulty sensor Tao
Faulty sensor Ts
Faulty sensor Td
Input overcurrent
Abnormal communication
between indoor and outdoor
units
System high pressure
protection
System low pressure
protection
IPM protection
EEPROM fault
Over hot protection of
compressor
Over hot protection of SPDU
(or ISPM)
DC fan motor fault
Faulty 4-way valve
switching on
Faulty sensor Tc
Faulty sensor Toci
Low voltage protection
High voltage protection
Abnormal communication
between main PCB and
SPDU(or ISPM)
Compressor be locked
Compressor vibration too big
Compressor lose position
Faulty compressor start
Faulty position checking
circuit
Compressor broken
Sensor disconnected, or broken, or short circuit
Sensor disconnected, or broken, or short circuit
Sensor disconnected, or broken, or short circuit
Sensor disconnected, or broken, or short circuit
Over current of the system, or broken of the current
sensor,or malfunction with indoor or outdoor fan
motors, or faulty PCB.
Wrong connection, or the wires be disconnected, or
wrong address setting of indoor units, or faulty PCB,
or faulty power supply
High pressure switch is disconnected, or high pressure
switch worked, or Tc too high and faulty outdoor fan
motor when cooling, or faulty indoor fan motors when
heating, or refrigerant overabundance
Low pressure switch is disconnected, or low pressure
switch worked, or Te too low and faulty outdoor fan
motors when heating, or faulty indoor fan motor when
cooling, or refrigerant shortage
IPM over current, or short circuit, or IPM temperature
too high, or IPM input voltage too low,or faulty SPDU
(or ISPM).
Faulty outdoor unit PCB
Serious lack of refrigerant of the system, or the
ambient temperature too high, or PMVs be blocked
Ambient tempreatrue too high, or outdoor fan be
blocked, or bad air circulation of outdoor unit
Fan is blocked, or the terminal is disconnected from
the PCB
Coil of 4-way valve is disconnected, or faulty outdoor
PCB
Sensor disconnected, or broken, or short circuit
Sensor disconnected, or broken, or short circuit
VDC<194V, too low voltage from power source
VDC>400V, too high voltage from power source
Communication cables broken, or not be well
connected, or faulty main PCB, or faulty SPDU(or
ISPM)
Faulty compressor or SPDU(or ISPM)
Faulty compressor
Faulty SPDU(or ISPM)
Faulty compressor or SPDU(or ISPM)
Faulty SPDU(or ISPM)
Faulty compressor or SPDU(or ISPM)
24
POSSIBLE REASONS