Applicable Extension Pipe For Each Model - Mitsubishi Electric PLA-RP-BA Technical Data Book

Hide thumbs Also See for PLA-RP-BA:
Table of Contents

Advertisement

8

APPLICABLE EXTENSION PIPE FOR EACH MODEL

8-1. PIPE LENGTH
8-1-1. 1:1 SYSTEM
Pipe length
<Table 1> Maximum pipe length
Liquid
OD
[6.35
pipe
Thickness
t0.8
(mm)
Gas
OD
[9.52
[12.7
pipe
Thickness
t0.8
t0.8
(mm)
10m
P71
[10m]
P100,P125,P140
<Marks in the table>
: It can be used.
: Cooling capacity is lowered.
: Additional refrigerant charge is required when
the pipe length exceeds 20m.
The maximum pipe length
50m
Charge-less pipe length
[30m]
8-1-2. TWIN AND TRIPLE SYSTEM
(1) TWIN SYSTEM
<Table 2> Maximum pipe length
P71(RP35o2)
Main pipe
Liquid pipe
[6.35
(mm)
[12.7
Gas pipe
[A]
Liquid pipe
[6.35
Gas pipe
[12.7
Branch
Liquid pipe
[9.52
pipe
(mm)
Gas pipe
[15.88
[B, C]
Liquid pipe
[12.7
Gas pipe
[19.05
Indoor unit
B
Distribution pipe
<TWIN SYSTEM>
Total length A + B + C
P71-140: 50 m
[9.52
[15.88
[12.7
[15.88
t1.0
t0.8
Standard size
10m
30m
[10m]
[30m]
[30m]
Standard size
[30m]
P100(RP50o2)
[9.52
[9.52
[9.52
[12.7
[15.88
[15.88
[19.05
[19.05
Standard size
Standard size
50m
50m
[30m]
[30m]
50m
50m
[30m]
[30m]
Indoor unit side
Indoor unit
C
Outdoor unit
Outdoor unit side
A
[12.7
t0.8
t0.8
[19.05
[15.88
t1.0
t1.0
t1.0
50m
30m
[20m]
50m
40m
[20m]
(2) TRIPLE SYSTEM
P125(RP60o2) • P140(RP71o2)
[9.52
[9.52
[12.7
[15.88
[19.05
[19.05
Standard size
50m
[30m]
Indoor unit
Distribution pipe
57
[19.05
t1.0
<Table 3> Maximum pipe length
P140(RP50o3)
Main pipe
[9.52
Liquid pipe
(mm)
[15.88
[A]
Gas pipe
Standard size
Liquid pipe
ø6.35
50m
Gas pipe
ø12.7
[30m]
Branch
Liquid pipe
ø9.52
pipe
50m
(mm)
Gas pipe
ø15.88
[30m]
[B, C, D]
Liquid pipe
ø12.7
Gas pipe
ø19.05
Indoor unit side
Indoor unit
B
C
D
Indoor unit
Outdoor unit side
A
<TRIPLE SYSTEM>
Total length A + B + C + D
P140: 50 m
[9.52
[12.7
[19.05
[19.05
Outdoor unit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents