Daikin R-410A Technical Data Manual page 21

Outdoor units
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

4
Capacity tables
4 - 1 Cooling/Heating capacity tables
FBQ35C7VEB + RXS35G2V1B
Cooling
Indoor
EWB
EDB
20
°C
°C
TC
SHC
PI
14.0
20
3.48
3.12
0.81
16.0
22
3.64
3.07
0.81
18.0
25
3.80
3.29
0.82
19.0
27
3.87
3.53
0.82
22.0
30
4.11
3.43
0.83
24.0
32
4.27
3.37
0.83
Heating
Indoor
EDB
-10
°C
TC
PI
15.0
2.69
0.96
20.0
2.55
0.99
22.0
2.50
1.00
24.0
2.44
1.01
25.0
2.42
1.01
27.0
2.36
1.02
S
YMBOLS
AFR
:
Air flow rate
BF
:
Bypass factor
EWB
:
Entering wet bulb temp.
EDB
:
Entering dry bulb temp.
TC
:
Total capacity
SHC
:
Sensible heat capacity
PI
:
Power input
• Outdoor Units • R-410A • RXS-G2V1B
25
TC
SHC
PI
TC
3.33
3.04
0.89
3.17
3.48
3.00
0.89
3.32
3.64
3.22
0.90
3.48
3.72
3.47
0.90
3.56
3.95
3.38
0.91
3.79
4.11
3.32
0.91
3.95
50Hz 220-240V
Outdoor temperature (°CWB)
-5
0
TC
PI
TC
PI
TC
3.14
1.01
3.60
1.05
4.14
3.01
1.03
3.46
1.08
4.00
2.95
1.04
3.40
1.09
3.94
2.90
1.05
3.35
1.10
3.89
2.87
1.06
3.32
1.11
3.86
2.81
1.07
3.26
1.12
3.81
(m3/min.)
(°C)
(°C)
(kW)
(kW)
(kW)
• Split Sky Air • Outdoor Units
50Hz 220-240V
Outdoor temperature (°CDB)
30
32
SHC
PI
TC
SHC
PI
2.97
0.97
3.10
2.94
1.00
2.93
0.97
3.26
2.91
1.00
3.16
0.98
3.42
3.14
1.01
3.41
0.98
3.49
3.39
1.01
3.33
0.98
3.73
3.31
1.02
3.27
0.99
3.89
3.25
1.02
AFR
16
6
10
PI
TC
PI
1.11
4.50
1.15
1.14
4.36
1.17
1.15
4.31
1.18
1.16
4.25
1.19
1.16
4.22
1.20
1.17
4.17
1.21
N
OTES
1
Capacities are based on the following conditions,
(1) Corresponding refrigerant piping length: 5m
(2) Level difference
2
shows nominal (rated) capacities and power input.
AFR
BF
35
40
TC
SHC
PI
TC
SHC
3.01
2.90
1.04
2.85
2.83
3.17
2.87
1.05
3.01
2.80
3.32
3.10
1.05
3.16
3.04
3.40
3.35
1.06
3.24
3.30
3.63
3.28
1.06
3.48
3.22
3.79
3.22
1.07
3.63
3.18
: 0m
3TW31272-3A
16
0.15
3
PI
1.12
1.13
1.13
1.13
1.14
1.15
4
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxs-g2v1b

Table of Contents