Installing the unit
Installing the remote controller
Connecting the wired remote controller cable to FTC
f Connect the wired remote controller cable to 5 and 6 on the terminal block (TB62) on the FTC controller.
f
• Wiring wire No.×size(mm2) : 2×0.3(polar)
• The 5m wire is attached as an accessory. Max. 500 m
NOTE
• Wiring size must comply with the applicable local and national codes.
• Circuit rating : DC12V
Circuit rating is NOT always against the ground.
Installing the wired remote controller
1. Select an installing position for the remote controller.
2. Procure the following parts locally :
• 2 piece switch box
• Thin copper conduit tube
• Lock nuts and bushings
6
Required clearances surrounding
the remote controller
Remote controller profile
30
30
46
Installation pitch
3. Seal the service entrance for the remote controller cable with putty
to prevent possible invasion of dew drops, water, cockroaches or
insects.
[A] For installation in the switch box
[B] For direct installation on the wall, select one of the followings:
• Prepare a hole through the wall to pass the remote controller
cable (in order to take out the remote controller cable from the
back), then seal the hole with putty.
• Take out the remote controller cable through the cut-out upper
case, then seal the cut-out notch with putty.
4. Connect the remote controller cable to the terminal block.
Conduit
Wall
Lock nut
Seal with putty
Bushing
Remote controller
Switch box
cable
[A]
Remote controller cable
Seal with putty
(To lead the remote controller cable from the back of
the controller)
Seal with putty
(To take out the remote controller cable through the
upper portion)
Remote controller cable
Wood screw
[B]
To TB62 No.5 and 6 on the FTC unit
TB6 (No polarity)
7