Honeywell ADEMCO LYNXR-ISIA Installation And Setup Manual page 38

Table of Contents

Advertisement

LYNXR-ISIA Installation and Setup Guide
✻ 80 Device Programming Menu Mode
The following explains these prompts in detail. The left two columns identify the prompts and list the
available entries. The right-most column provides a further explanation of the entries.
Note: Entering a number other than one specified will give unpredictable results.
Powerline Carrier Device
80
programming
0 = exit mode
1 = enter mode
Device number
01-08 = device number to be programmed
A
0I
[✻] = continue
00 = exit Device Programming mode
Device action
b
aa
0 = No response
1 = Close for 2 seconds
2 = Close and Stay Closed
3 = Continuous Pulse on & off (1 sec ON, 1 sec
OFF)
[✻] = continue
[#] = return to previous prompt
Start event type
et
0 = Not used
C
1 = Alarm
2 = Fault
Start zone list
zl
d
1-3 = zone list number (to be programmed in
0 = zone list not used for this device
[✻] = continue
[#] = return to previous prompt
Start zone type
01-58 = zone type to start this device action
E
zt
00 = zone type not used for this device
[✻] = continue
[#] = return to previous prompt
Stop zone list
zl
1-3 = zone list to stop this device action
F
0 = zone list not used
[✻] = continue
[#] = return to previous prompt
Stop zone type
zt
01-58 = zone type to start this device action
IA
00 = zone type not used for this device
[✻] = continue
[#] = return to previous prompt
3 = Trouble
[✻] = continue
[#] = return to previous
prompt
field ✻81)
(select only those that are applicable)
(select only those that are applicable)
Entering "1" advances to the next prompt below.
Entering "0" exits mode, upon which this prompt blinks, indicating
the mode is inactive.
Enter device numbers as 2-digit entries.
Enter the 1-digit action (0-3) for the device being programmed
(current action is displayed).
NOTES:
1. If "3" is entered (pulse), only up to 3 different devices can be
pulsed if one of the devices is a siren/horn (X10 Powerhouse
Security model SH10A). In addition, the siren/horn cannot be
manually activated using the lights on/lights off keypad
commands.
2. If using an X10 Powerhouse Security SH10A siren:
• you must use device action "3."
• you must change the device action default to "3" if using default
table 2 or 4
Enter the 1-digit event type (0-3) to activate the device being
programmed. A zone list must be used in conjunction with an event. If
a zone type/system operation is to be used instead of an event, enter
"0".
If a zone list will be used to start the device action, enter the zone list
number at this prompt.
If a zone type or system operation will be used to start the device
action, enter the appropriate 2-digit code for the device being
programmed (see table that follows).
Choices for zone types
00 = Not Used
01 = Entry/Exit #1
02 = Entry/Exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24 Hr Silent
Choices for system operation
20 = Arming–Stay
21 = Arming–Away
22 = Disarm. (Code + OFF)
31 = End of Exit Time
32 = Start of Entry Time
33 = Any Alarm (except zt 08 or 09)
36 = At Bell Timeout**
** Or at Disarming (which ever occurs earlier)
SIA
ZT 16 must be used in SIA fire applications.
If a zone list will be used to STOP, or restore, the device action, enter
the zone list number 1, 2, or 3 (to be programmed in
used, enter "0".
If a zone type or system operation will be used to STOP the device
action, enter the appropriate 2-digit code (see the "ZT" choices listed
above). If not, enter 00.
The display then returns to the DEVICE NUMBER prompt (A) so
that you can enter the next device number to be programmed, or enter
[0][0] to end device programming.
- 38 -
07 = 24 Hr Audible
08 = 24 Hr Aux
09 = Fire without verification
10 = Interior w/Delay
16 = Fire with verification
24 = Silent Burglary
38 = Chime
52 = Kissoff
39 = Any Fire Alarm
40 = Bypassing
42 = System Battery Low
43 = Communications Failure
58 = Duress
81 mode). If not

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents