Mitsubishi Electric FR-E700 Installation Manuallines page 25

Fr-e740-016 to 300-ec
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

A.2 Instructions for UL and cUL
(UL 508C, CSA C22.2 No.14)
A.2.1 General precaution
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10
minutes, and check for residual voltage between terminal P/+ and N/− with a meter etc., to avoid a hazard of electrical shock.
A.2.2 Installation
The below types of inverter have been approved as products for use in enclosure and approval tests were conducted under the
following conditions.
Design an enclosure so that the inverter ambient temperature, humidity and atmosphere satisfy the specifications. (Refer to
Wiring protection
For installation in the United States, branch circuit protection must be provided in accordance with the National Electrical
Code and any applicable provincial codes.
For installation in Canada, branch circuit protection must be provided in accordance with the Canada Electrical Code and
any applicable provincial codes.
Provide the appropriate UL and cUL listed class T type fuse that are suitable for branch circuit protection in accordance
with the table below.
FR-E740-
-EC (C)
Rated voltage [V]
Without power factor
Fuse maximum
improving reactor
allowable
With power factor
rating [A] *
improving reactor
* Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
A.2.3 Short circuit ratings
400V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100kA rms Symmetrical Amperes, 528V Maximum.
A.2.4 Wiring
The cables used should be 75°C copper cables.
Tighten the terminal screws to the specified torques.
Undertightening can cause a short or misoperation.
Overtightening can cause the screws and unit to be damaged, resulting in a short or misoperation.
Use the UL approved round crimping terminals. Crimp the terminals with the crimping tool recommended by the terminal
manufacturer.
016
026
040
6
10
15
6
10
10
060
095
120
480V or more
20
30
40
15
25
35
APPENDIX
.)
page 2
170
230
300
70
80
90
60
70
90
21

Hide quick links:

Advertisement

Table of Contents
loading