Do not discharge refrigerant into the atmosphere if refrigerant leaks during installation, ventilate the room.
Use appropriate tools for high pressure refrigerant.
When pumping down refrigerant , stop the compressor before disconnecting the refrigerant pipes.
During installation securely fasten the refrigerant pipes before starting the compressor.
Check that refrigerant gas does not leak after the completion of installation.
Use R410A refrigerant only. Do not allow air to enter the lines. Failure to observe these instructions will cause mechanical failure, system failure or, in the worst
case, serious breach of product safety.
<Using R410A refrigerant heat pumps>
Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, to connect the refrigerant pipes. Make sure the insides of the pipes are clean and
do not contain any harmful contaminants such as sulfuric compounds, oxidants, debris, or dust. Use pipes with the specifi ed thickness. (Refer to 4.4 in the instal-
lation manual.) Note the following if reusing existing pipes that carried R22 refrigerant.
- Replace the existing fl are nuts and fl are the fl ared sections again.
- Do not use thin pipes. (Refer to 4.4
Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing. (Leave elbow joints, etc. in their packag-
ing.) If dust, debris, or moisture enters the refrigerant lines, oil deterioration or compressor breakdown may result.
Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil applied to the fl ared sections. If mineral oil is mixed in the refrigeration oil, oil dete-
rioration may result.
Do not use refrigerant other than R410A refrigerant. If another refrigerant is used, the chlorine will cause the oil to deteriorate.
Use the following tools specifi cally designed for use with R410A refrigerant. The following tools are necessary to use R410A refrigerant. Contact your nearest
dealer for any questions.
Tools (for R410A)
Gauge manifold
Charge hose
Gas leak detector
Torque wrench
Be sure to use the correct tools. If dust, debris, or moisture enters the refrigerant lines, refrigeration oil deterioration may result.
Do not use a charging cylinder, a cylindrical measuring container, when charging R410A refrigerant gas. If the refrigerant gas is transferred to a charging cylinder,
the composition of the refrigerant will change and system effi ciency will be reduced.
OCH532A
WARNING (SPLIT MODELS ONLY)
CAUTION (SPLIT MODELS ONLY)
in the installation manual.
)
Flare tool
Size adjustment gauge
Vacuum pump adapter
Electronic refrigerant charging scale