Operation Characteristics
4-1 NON INVERTER
1
Cooling Mode Operation
When selecting the Cooling Mode
Operation, the unit will operate according
to the setting by the remote controller and
the operation is as well as the following.
Room temperature can be set in 1°C
steps in the range of 18 to 30°C.
2
Heating Mode Operation
When selecting the Heating Mode
Operation, the unit will operate according
to the setting by the remote controller and
the operation is as well as the following.
Room temperature can be set in 1°C
steps in the range of 16 to 30°C.
3
Automatic Operation
When Automatic operation is set by the remote controller, the air conditioner senses the room
temperature then automatically selects the operation mode and setting temperature.
Room Temp ≥ 21°C + ∆T
Room Temp < 21°C + ∆T
In case that Room Temp. ≥ 21°C + ∆T, The Unit is operated in the Cool Mode.
In case that Room Temp. < 21°C + ∆T, The Unit is operated in the Heat Mode.
∆T means that user is able to change setting temperature within ±2°C.
Room Temp.(°C)
Ts+1
Ts
Compressor
♦ Ts means Remote Controller setting Temperature
Room Temp.(°C)
Ts+5
Ts+3
Compressor
Operating Mode
Cooling
Heating
On
Off
On
Off
Setting Temp.
Tsp = 24°C + ∆T
∆T = -2, -1, 0, 1, 2
Tsp = 22°C + ∆T
Time
On
Time
On
Remarks