TS2500 Hints and Tips

Output Modules

The Output Module provides eight switched negative
outputs capable of supplying 100mA each to drive LEDs
or miniature relays. You can daisy chain up to 128
Ouput Modules together, connecting the first one to the
Ouput Module connector JP2 on the control panel
main pcb.
Programming OM Options (Engineers Menu
4 option 7)
There are two sub-options in this command: ward
mimic and circuit mimic.
Ward mimic provides a list of ward information that you
can send to the output modules. The control panel
transmits every item in the list that you say yes to. The first
output module picks up the first item transmitted, the
second module picks up the second item, and so on.
Circuit mimic provides eight blocks of circuit numbers
that you can select. For each block you choose the
starting and ending circuit number. A block can cover
all the circuits connected to the panel, or a single
circuit. The control panel sends all the selected circuits
To control
panel
Ward Bell A-H
No. Mimic Option
00
Ward A-H Bell SAB
01
Ward I-P Bell SAB
02
Ward A-H Strobe
03
Ward I-P Strobe
04
Ward A-H SW12V
05
Ward I-P SW12V
81
Internal Digi
Circuit Mimics
Start 1 1001
Start 2 2001
8
Ward Strobe A-H
To Control Panel
Yes/No
Yes
No
Yes
No
No
No
No
End 1 1008
End 2 2008
Figure 5. Output Mocule Example
to the output modules remaining after those used by
the ward mimic infomation. Each LED corresponds to a
circuit.
Example
Figure 5 shows an example using four Output Modules.
During programming Mimic Options 00 and 02 have
been selected as Yes. All other Mimic Options are No.
This means that Output Module 1 will respond to Ward
A-H Bell and Output Module 2 will respond to Ward A-H
Strobe.
In the example two blocks of circuits have been
defined. Start 1/End 1 specifies circuits 1001 to 1008
and Start 2/End 2 specifies circuits 2001 to 2008. This
means that Output Modules 3 will respond to circuits
1001 to 1008, and Output Module 4 will respond to
circuits 2001 to 2008.
Output Modules Connected to XNodes
Each XNode is capable of driving one, and only one,
Output Module. When connected to an XNode an
Output Module mimics the eight circuits of that XNode,
and no others.
Circuit Mimic
1001-1008
Wards
Wards
A-H Bell
A-H Strobe
OM 1
OM 2
Circuit Mimic
2001-2008
Circuit Mimic
Circuit Mimic
1001-1008
2001-2008
OM 3
OM 4