Outdoor model
Outdoor unit power supply
Indoor units number
Piping total length
Connecting pipe length
Height difference (Indoor ~ Outdoor)
Height difference (Indoor ~ Indoor)
Function
Capacity [Rated (Min.-Max.) Hz
Dehumidification
Outdoor air flow
Breaker capacity
Running current
Power input
Power factor
Starting current
Compressor motor current
Fan motor current
Coefficient of performance(C.O.P)
Model
Output
Winding
resistance(at 20 °C)
Model
Winding
resistance(at 20 °C)
Dimensions W x H x D
Weight
Sound level
Fan speed
Refrigerant filling
capacity(R410A)
Refrigeration oil (Model)
1 Measured under rated operating frequency.
2 Electrical data is for only outdoor unit.
NOTE: Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m)
COOLING INDOOR
Dry-bulb temperature 27.0°C Wet-bulb temperature 19.0°C
OUTDOOR Dry-bulb temperature 35.0°C Wet-bulb temperature 24.0°C
HEATING INDOOR
Dry-bulb temperature 20.0°C
OUTDOOR Dry-bulb temperature 7.0°C
OBH584E
m
m
m
Refer to 7 REFRIGERANT SYSTEM DIAGRAM.
Refer to 7 REFRIGERANT SYSTEM DIAGRAM.
m
Cooling
10.0 (3.9 - 11.0)
kW
/h
3,396
m
/h
3
A
12.30
A
2,800
W
%
A
12.1
A
A
3.57
W
Ω
Ω
5C100VA
mm
5C100VA2
5C100VA
kg
5C100VA2
51
dB
720
rpm
kg
L
Wet-bulb temperature 6.0°C
12
MXZ-5C100VA MXZ-5C100VA2
Single phase
230 V, 50 Hz
1 to 5
Max. 80
Max. 25
25
99
12.45
0.2
TNB220FMCH
2,700
U-V 1.41
V-W 1.41 W-U 1.41
RC0J60-CA
BLK-WHT 15.2
WHT-RED 15.2 RED-BLK 15.2
900 x 900 x 320
900 x 915 x 320
68
70
4.0
0.87 (NEO22)
Heating
12.0 (4.1 - 14.0)
3,558
12.45
2,835
12.25
4.23
54
750

Advertisement