Panasonic CS-C18DKD Service Manual page 37

Table of Contents

Advertisement

Attached accessories
Applicable piping kit
CZ-4F5, 7, 10AN (C18DK)
SELECT THE BEST LOCATION
INDOOR UNIT
• There should not be any heat source or steam near the
unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
• Recommended installation height for indoor unit shall be
at least 2.3 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short
circuit of the discharged air.
• If piping length is over 7.5m, additional refrigerant
should be added as shown in the table.
REMOTE CONTROL
• Do not install at place where there is direct sunlight or
near any heat source.
Indoor/Outdoor Unit Installation Diagram
• This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
37
CS-C18DKD CU-C18DKD / CS-C24DKD CU-C24DKD

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu-c24dkdCu-c18dkdCs-c24dkd

Table of Contents