GENERAL DESCRIPTION

The GEM-RS232 Control Panel/ Computer Converter is
an interface module which allows the NAPCO GEM-P9600
control panel to be connected to a computer which may be
used to display system status. The GEM-RS232 is
approved by Underwriters Laboratories for supplemental
use only. It provides signal and ground isolation between
the control panel and the computer and will protect the
control panel from shorts, transients and surges which may
emanate from the computer or the associated cabling.
The GEM-RS232 has been designed to be permanently
mounted inside the cabinet of the GEM-P9600 and can be
connected to the computer in several different fashions
(see CONNECTION).

SPECIFICATIONS

Input Power: 12 V DC nominal, 60 mA (supplied by control
panel connections)
Note: Reduce available panel combined auxiliary current
by 60 mA)
Dimensions: 11/16" x 2 9/16" x 2 9/16" (HxWxD)
Range: 50 feet using RS232 serial cable
100 feet using Cat5 cable

ORDERING INFORMATION

1. GEM-RS232
RS232 Converter
6 conductor Modular to Modular (RJ12 Style) cable
1 SE-AUTOMATION EPROM
2. GEM-RS232KIT
RS232 Converter
6 conductor Modular to Modular (RJ12 Style) cable
8 Pin Modulator (RJ45 Style) to DB9 Male Adapter
8 Pin Modulator (RJ45 Style) to DB9 Female
Adapter
1 SE-AUTOMATION EPROM
Control Panel / Computer Converter

INSTALLATION INSTRUCTIONS

NAPCO Security Systems, Inc.
333 Bayview Avenue, Amityville, New York 11701
For Sales and Repairs, call toll free: (800) 645-9445
For direct line to Technical Service, call toll free: (800) 645-9440
Internet: http://www.napcosecurity.com
GEM-RS232

SYSTEM REQUIREMENTS

The following system hardware is required:
Gemini GEM-P9600 Control Panel
SE-AUTOMATION EPROM Upgrade must be
installed in control panel.

MOUNTING INSTRUCTIONS

1
Open GEM-RS232 case using screwdriver.
2
Drill hole in the center of the base of the case
(side without label) using a 1/8" drill bit.
3
Drill hole in housing using a 1/8" drill bit
4
Mount securely using nut and screw provided

CONNECTION

Refer to the wiring diagram. Connect the 6-conductor
modular cable (supplied) to J1 (RJ12 style) of the
control panel and then plug into the module (RJ12
style) plug on the RS232 converter.
For direct connection to serial port of computer or
automation system, plug male DB9 connector of
serial cable (NOT supplied) into the DB9 connector
of the RS232 converter and connect other end to
serial port of computer.
For CAT 5 wiring to computer or automation system,
plug male DB9/CAT5 connector (supplied with
GEM-RS232KIT) into the DB9 connector of the
RS232 adapter and connect female DB9/CAT5
connector (supplied with GEM-RS232KIT) to
automation system DB9 connector. Use CAT5
cable terminated with standard RJ45 connectors
(not supplied).
WI966 6/99
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GEM-RS232 and is the answer not in the manual?

Questions and answers

Summary of Contents for NAPCO GEM-RS232

  • Page 1: Installation Instructions

    NAPCO GEM-P9600 control panel to be connected to a computer which may be used to display system status. The GEM-RS232 is approved by Underwriters Laboratories for supplemental use only. It provides signal and ground isolation between...
  • Page 2 This Warranty gives you specific legal rights and you may also have other rights which vary from state to state. Cable Connecting GEM-RS232 to Computer DB9 to DB9 serial cable (NOT supplied)

Table of Contents