Panasonic CS-HE9JKE Service Manual page 70

Table of Contents

Advertisement

15.4.22. F96 (IPM Overheating)
Malfunction Decision Conditions
During operating of cooling and heating, when IPM temperature data (100°C) is detected by the IPM temperature sensor.
Multi Models Only
• Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated.
• Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is detected by the
heat sink temperature sensor.
Malfunction Caused
• IPM overheats due to short circuit of hot discharge air flow.
• IPM overheats due to defective of outdoor fan motor.
• IPM overheats due to defective of internal circuitry of IPM.
• IPM overheats due to defective IPM temperature sensor.
Multi Models Only
- Compressor OL connector poor contact.
- Compressor OL faulty.
Troubleshooting
70

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents