Download Print this page

Trane 4TWR3 Installer's Manual page 6

Hide thumbs Also See for 4TWR3:

Advertisement

|nsta||er's
Guide
SUBCOOMNG
CHARGING
iN COOLING
ABOVE 55°F OD AMBIENT
The Trane company
has always
recommended
installing
Trane approved
matched
indoor and outdoor
systems.
All Trane split systems
are ARI rated with only TXV indoor
systems.
The benefits
of installing
approved
indoor and outdoor split
systems
are maximum
efficiency,
optimum
perfbrmance
and
the best overall system
reliability.
The fbllowing charNng
methods
are therefore
prescribed
fbr systems
with indoor TXVs.
1. Subcooling
(in the cooling mode) is the on__a!y_l
recommended
method
of charging
above
55°F ambient
temperatures.
2. For best results
- the indoor temperature
should be kept between
70°F to 80°F. Add
system
heat if needed.
3. At start-up,
or whenever
charge is removed
or added, the system
must be operated
for a
minimum
twenty
(20) minutes
to stabilize
befbre accurate
measurements
can be made.
4. Measure
Liquid Line Temperature
and
Refrigerant
Pressure
at service valves.
5. Determine
total refrigerant
line length,
and height
(lift) if indoor section
is above
the condenser.
6. Determine
the Design Subcool Charging
Temperature
from the unit nameplate.
7. Locate this value in the appropriate
column
of the Subcooling
Charging
Table. Locate
your liquid line temperature
in the left
column of the table, and the intersecting
liquid line pressure
under your nameplate
subcool value column.
Add refi'igerant
to
raise the pressure
to match
the table, or
LIQUID
TEMP
(°F)
remove refrigerant
to lower the pressure.
Again, wait
twenty
(20) minutes
for the system
conditions
to stabilize
before adjusting
charge again.
8. When system
is correctly
charged,
you can refer to
System
Pressure
Curves (in Service Facts)
to verify
typical perfbrmance.
R=410A REFRIGERANT
CHARGING CHART
DESIGN SUBCOOLING (°F)
8 I 9 I 10 I 11 ! 12 I la I 14
LIQUID
GAGE
PRESSURE
(PSI)
55
179
182
185
188
191
195
198
60
195
198
201
204
208
211
215
65
211
215
218
222
225
229
232
70
229
232
236
240
243
247
251
75
247
251
255
259
263
267
271
80
267
271
275
279
283
287
291
85
287
291
296
300
304
309
313
90
309
313
318
322
327
331
336
95
331
336
341
346
351
355
360
100
355
360
365
370
376
381
386
105
381
386
391
396
402
407
413
110
407
413
418
424
429
435
441
115
435
441
446
452
458
464
470
120
464
470
476
482
488
495
501
125
495
501
507
514
520
527
533
From Dwg. D154557P01
Rev. 2
SUBCOOL
CHARGING
TABLE
CORRECTIONS
FOR LINE LENGTH
AND RISE
_w
Zw
<EL
CC'_
ELW
wZ
rr-7
0 Subtract 10 psig from S.C. Table Pressure
10
20
25
30
40
60
TOTAL
REFRIGERANT
LINE LENGTH
(FEET)
8O
SUBCOOLING
CHARGING
BELOW 55°F OD AMBIENT - IN HEATING ONLY
1. The Subcool Charging
Method in cooling is not recom-
mended
below 55°F outdoor ambient.
2. The only recommended
method
of charging
at outdoor
ambients
below 55°F, is to weigh in the charge in the
heatin_
mode.
3. Use Nameplate
charge
plus standard
charge
adders fbr
line length.
4. Check liquid line temperature
and pressure
(at the
OD valves) to obtain a minimmn
of 10°F subcooling.
5. Add chaige ifa minimum
of 10°F subcooling is not obtained
with the nameplate
charge
plus line length correction.
6. It is important
to return
in the spring or summer
to
accurately
charge
the system in the cooling mode at
outdoor ambients
above 55°F.
6
18-BC51 D1-5

Advertisement

loading

This manual is also suitable for:

4twr4