Murphy Selectronic Micro-Controller/Annunciator Series 1501 Specifications

Micro-controller/annunciator

Advertisement

Quick Links

Series 1501 Selectronic
Micro-Controller/Annunciator
Description
The Series 1501 instrument is a microprocessor-
based alarm, shutdown and control system with
tachometer/hourmeter function. It annunciates
in alphanumeric characters the protective device
that has signaled an alarm or caused equipment
shutdown. Information is called up and adjust-
ments are made on a six-button keypad on the
face of the unit. Configurations such as: Alarm
or Shutdown Nomenclature, Preset Timers, and
Tachometer Calibration can be made in the
field.
Murphy's Series 1501 system has seven SPDT
relays. On the standard model, the relays are
assigned to the following functions: Lube,
Crank, Ignition/Motor, Fuel Valve, Load,
Alarm, Shutdown.
The complete Series 1501 system consists of a
head (monitor), sensor input terminal strip (two
needed for 64 sensor models), 36 inch (914
mm) flat ribbon cable(s) for connecting the ter-
minal block to the head/monitor, and a Class I,
Div. 1, explosion-proof power supply.
The Series 1501 system is powered from 120
VAC
12 or 24 VDC. The head/monitor is rated intrin-
sically safe and includes a communication port:
RS232 or RS485 (Modbus RTU slave). This
port allows for remote control functions such as
Start/Stop, Load/Unload, etc., and for access to
Series 1501 registers.
Alarm/Shutdown for 32 or 64 N.O. or N.C. Sensors
Operating Sequence Selection
Field Adjustable Sensor Nomenclature
Selectable Sensor Lockouts Class A, B, C or P
Built-In Tachometer/Overspeed Function
RS232 or RS485 Modbus RTU Communications
Two Start/Run Timers and Elapsed Time Meter
CSA Certified or NRTL Approved for Use in
Class I, Div. 1 Grps. C & D Hazardous Locations
NRTL/C
Applications
The Series 1501 system can be configured to mon-
itor applications such as: Air and Gas
Compressors, Natural Gas Refueling, and other
Industrial Operations. For a list of applications and
our cataloged programs contact a Murphy sales
representative. Custom programming available at
additional charge.
Features
32 or 64 sensor inputs (N.O. or N.C.) for
alarm or shutdown.
Easy operation/adjustments Six-button keypad.
RS232 or RS485 Modbus RTU communica-
tions.
Automatic Engine Control.
Two Start-Run Timers.
Seven Control Relay Outputs.
Pre/Postlube Time Delay.
Automatic Compressor Loading.

Specifications

Power Consumption: 120 VAC (7.5 VA);
12 VDC (3.5 watts); 24 VDC (3.5 watts).
Sensor Inputs: 32 to 64 N.O. and/or N.C. inputs
such as Murphy Swichgage
Field selectable as a Class A, B1, B2 , C , P or
or
ESD for shutdown, alarm, or control function.
Outputs: 7-SPDT relay outputs, 5 A, 1/16 HP,
125/250 VAC/ 1 A, 30 VDC.
NOTE: For hazardous areas an approved isola-
tion barrier must be used between sensor switch
and input terminals if the sensor output comes
from any energy storing device such as a relay or
transistor.
S15-96122B page 1 of 2
®
Adjustable Time Delays:
(standard Series 1501)
Prelube
Process Delay
Run Delay
Purge
Fuel Delay
Load Delay
Class B1 Sensor Lockout
Class B2 Sensor Lockout
Before Ignition Ground or Electric Motor
Stop (for up to 59 seconds)
Sensor Inputs Terminal Block: Rail mount
DIN type; 32 terminals, screw type.
Opto-Isolated Tach/Run Input: Magnetic
pickup, 4.5 to 120 Vrms, 0-10 kHz. CD igni-
tion, positive or negative ground, 100 to 300
VDC, 3-666 Hz. 12 to 125 VDC or 120 Vrms,
50/60 Hz may be used for run signals.
Operating Temperatures: 32 to 122°F
(0 to 50°C).
Storage Temperatures: -4 to 158°F (-20 to 70°C).
Case: ABS plastic, 1/4 DIN (90 x 90 mm).
Interface Output: Factory configured for
RS232; field-selectable for RS485 (specify
for factory configured RS485).
Alphanumeric Display: 2 lines, each line with
®
instruments.
16 characters (32 characters total).
Power Supply Enclosure: Explosion-proof,
Class I, Division 1. Intrinsically safe barrier
built into the power supply, 120 VAC with 7
form "C" relay outputs for the following
functions (with standard S1501):
Lube
Ignition/Motor
S15-96122B
Revised 07-06
Catalog Section 50
Rest
Permissive
Idle/Cooldown
Postlube
Crank
Test
Load
Crank
Alarm
Shutdown
Fuel Valve

Advertisement

loading
Need help?

Need help?

Do you have a question about the Selectronic Micro-Controller/Annunciator Series 1501 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Murphy Selectronic Micro-Controller/Annunciator Series 1501

  • Page 1: Specifications

    Shutdown Nomenclature, Preset Timers, and Tachometer Calibration can be made in the field. Murphy’s Series 1501 system has seven SPDT relays. On the standard model, the relays are assigned to the following functions: Lube, Crank, Ignition/Motor, Fuel Valve, Load, Alarm, Shutdown.
  • Page 2: How To Order

    MURPHY, the Murphy logo, and Selectronic mon law trademarks of Murphy Industries, Inc. This document, including textual matter and illustrations, is copy- right protected by Murphy Industries, Inc., with all rights reserved. (c) 2006 Murphy Industries, Inc.