Mitsubishi Electric PURY-EP200 Service Handbook page 225

Hide thumbs Also See for PURY-EP200:
Table of Contents

Advertisement

[ IX Troubleshooting ]
1. Error Code
5301
ACCT sensor fault (Detail code 115)
2. Error definition and error detection method
When the formula "output current < 1.5 Arms" remains satisfied for 10 seconds while the inverter is in operation.
3. Cause, check method and remedy
Cause
(1)
Inverter open output phase
(2)
Compressor failure
(3)
INV board failure
Refer to section -7-"Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 283)
1. Error Code
5301
ACCT sensor circuit fault (Detail code 117)
2. Error definition and error detection method
When an error value is detected with the ACCT detection circuit just before the inverter starts
3. Cause, check method and remedy
Cause
(1)
INV board failure
(2)
Compressor failure
Refer to section -7-"Inverter" under part [4] Troubleshooting Principal Parts for error codes related to the inverter.(page 283)
HWE0713A
Check method and remedy
Check the output wiring connections.
Refer to IX [4] -7- (2) [2].(page 285)
Refer to IX [4] -7- (2)[1], [3], [4].(page 285)
Check method and remedy
Refer to IX [4] -7- (2)[1], [3], [4].(page 285)
Refer to IX [4] -7- (2) [2].(page 285)
- 216 -
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents