Mitsubishi Electric MFZ-KA-VA Technical Data Book page 43

Heat pump air conditioners
Hide thumbs Also See for MFZ-KA-VA:
Table of Contents

Advertisement

PCA-RP50KA
PCA-RP60KA
[
LEGEND
]
SYMBOL
NAME
I.B
INDOOR CONTROLLER BOARD
CN2L
CONNECTOR (LOSSNAY)
CN32
CONNECTOR (REMOTE SWITCH)
CN41
CONNECTOR (HA TERMINAL-A)
CN51
CONNECTOR (CENTRALLY CONTROL)
FUSE
FUSE (T6.3AL250V)
LED1
POWER SUPPLY (I.B)
LED2
POWER SUPPLY (R.B)
LED3
TRANSMISSION (INDOOR-OUTDOOR)
SW1
SWITCH (MODEL SELECTION)
SW2
SWITCH (CAPACITY CODE)
SWE
CONNECTOR (EMERGENCY OPERATION)
X1
RELAY (DRAIN PUMP)
R.B
WIRED REMOTE CONTROLLER BOARD
REACTOR
DCL
MF
FAN MOTOR
MV
VANE MOTOR
I.B
VANE CNV (WHT)
20
18
16
14
12
10
8
6
4
2
19
17
15
13
11
9
7
5
3
1
WIRELESS
CN90
(WHT)
1
9
9
CNB
BZ
5
SW1
LED2
M
SW2
LED1
MV
RU
W.B
(OPTIONAL PARTS)
Notes:
1. SymboIs used in wiring diagram above are,
2. Indoor and outdoor connecting wires are made with poIarities, make wiring matching terminal numbers (S1, S2, S3).
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires (specification of 230V), adopting superimposed system
for power and signal.
: For power supply system of this unit, refer to the caution label located near this diagram.
PCA-RP71KA
SYMBOL
TB4
TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TB5,TB6
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
TH1
ROOM TEMP. THERMISTOR
(0°C / 15kΩ, 25°C / 5. 4kΩ DETECT)
TH2
PIPE TEMP. THERMISTOR/LIQUID
(0°C / 15kΩ, 25°C / 5. 4kΩ DETECT)
TH5
COND. / EVA. TEMP. THERMISTOR
(0°C / 15kΩ, 25°C / 5. 4kΩ DETECT)
OPTIONAL PARTS
See table 1
W.B
PCB FOR WIRELESS REMOTE CONTROLLER
See table 2
BZ
BUZZER
LED1
LED (OPERATION INDICATION : GREEN)
LED2
LED (PREPARATION FOR HEATING : ORANGE)
RU
RECEIVING UNIT
SW1
EMERGENCY OPERATION (HEAT / DOWN)
SW2
EMERGENCY OPERATION (COOL / UP)
DP
DRAIN PUMP
FS
DRAIN FLOAT SWITCH
Refer to tables 1 and 2
TRANSMISSION
2
1
WIRES
TB6
DC12V
R.B
J41
J42
CN32
SW1
SW2
(WHT)
1
CN51 (WHT)
Pair No.
5
1
CN41 (WHT)
CN2L
2 1
4
1
LED3
LED2
LED1
SWE
ON OFF
FLOAT SW
CN4F
(WHT)
1
4
When attaching
When attaching
drain pump
drain pump
(optional parts),
(optional parts)
remove the jumper
connector CN4F
1
and fit the drain
FLOAT SW
CN4F
float switch (FS).
(WHT)
FS
:Connector,
NAME
TB5
2
1
OUTDOOR
CN01
3
(
)
BLK
1 3
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(
BLU
)
1
2
REMOCON
CN22
DC311~339V
(
)
BLU
RECTIFICATION
LIQUID/PIPE
INTAKE
FAN
CN44
CN20
CNMF
(WHT)
(RED)
(WHT)
3
1
2
7
4
1
1
4
M
MS
1~
3~
DP
TH2 TH5
TH1
MF
(OPTIONAL PARTS)
Be sure to turn off the source power
4
and then disconnect fan motor connector.
(Failure to do so will cause trouble in Fan motor)
<Table 1> SW1
<Table 2> SW2 (CAPACITY CODE)
(MODEL SELECTION)
MODELS
SW1
Service
PCA-RP50KA
1 2 3 4 5
ON
OFF
PCA-RP60KA
PCA-RP71KA
The black square (■) indicates a switch position.
:Terminal (block).
43
DCL
YLW
1 3 5
FUSE
TB4
YLW
YLW
S1
TO OUTDOOR
ORN
ORN
X1
S2
UNIT
S3
D.U.M
ORN
1
CNP
BRN
(BLU)
SW2
Service
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
ON
OFF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents