11-1. Switch setting
How to set the switches is explained below, using an example of how to set the item No. 250 "(0) Initial setting data and User
info data ".
Steps
Setting item
Select the item No. Set SW601 to [1111 1010].
1
2
Enter a value.
Save the setting.
3
Switch Board
M-NET Board
TB3
Setting method
Set SW606 (upper digit) to "0", and SW607 (lower digit) to "0". [ 0 ]
Press and hold SW605 for three seconds.
MAIN Board
TB1
Detail setting switch
(Use to select items)
Detail setting switch
(Use to save the settings)
- 27 -
[ _ 250] will appear for one second, and the
SW606 and SW607 preset values will appear.
[ End ] will appears after [ 0 ] blinks.
Reset the setting when [ Err_ ] is displayed.
7-segment LED
SW601
SW605
7-segment LED display
USB port
SW606, SW607
Detail setting switch
(Use to select values and
items to be displayed on the LED)