Honeywell Prestige THX9321 System Installation Manual page 7

Hide thumbs Also See for Prestige THX9321:
Table of Contents

Advertisement

Install
optional
sensors
[If no sensors
are used,
skip
to Section
7.]
THX9321/9421
Prestige _ IAQ and RF ElM
To install outdoor air sensor
1
Mount
the sensor
on a vertical
exterior
wall,
at least 6 inches
below
any overhang.
Choose
a location
protected
from
direct
sunlight.
2
Place
sensor
securely
in bracket,
facing
away
from
wall.
M2_4_,
To install indoor air sensor
1
Remove
the waltptate
and mount
it 4
to 6 feet above
the floor
on an interior
watt. Drill 3/16=inch
holes for drywall,
7/32=inch
for plaster.
2
Attach
sensor
securely
to watlplate
as
shown.
M32936
To install discharge/return
air sensor
1
Instalt the sensor
between
the IAQ
equipment
and the heating/cooling
equipment.
The sensors
must
be in air
that is mixed
well
(away from
a=coiV
heat
exchanger).
2
Drill 1/4=inch
hole for the sensor
probe
and mount
it to the ductwork
with
enclosed
screws.
Connect wires to Sl or S2 terminals
at
the ElM.
Z
69-2490--03