CleaRanCeS
CleaRanCeS To CoMBuSTIBleS
Follow these instructions carefully to
ensure safe installation. Failure to follow
instructions exactly can create a fire
hazard.
The appliance cannot be installed on a
carpet, tile or other combustible material
other than wood flooring. If installed on
carpet or vinyl flooring, the appliance
shall be installed on a metal, wood or
noncombustible material panel extending
full width and depth of the appliance.
72"
Minimum
Side
Wall
6"
Minimum
Figure 5 -
Ceiling and Side Wall Clearances
ManTel CleaRanCeS
fP2032
wall clearances
noTe: The combustible area above the facing must
not protrude more than 3/4" from the facing. If it does,
it is considered a mantel and must meet the mantel
requirements listed in this manual.
never obstruct or modify the air inlet or
outlet grilles (louvers). This may create
a fire hazard.
69D3011
CDVSC7 & CDV7 Series Gas Fireplace
Finish Wall
W
A
Top of Heat
Exhaust Vent
CDV33/42/47
Side View
Ref.
CDV33
A 14" (356 mm) 1" (305 mm) W 1" (305 mm) 1" (305 mm)
B 11" (79 mm) 9Z\x" (41 mm) X
C 10" (54 mm) 8Z\x" (16 mm) Y
D
8" (03 mm)
Finish Wall
12" (305 mm)
13"
(330 mm)
Top of Heat
Exhaust Vent
CDV36
Side View
FP03
FP86
Side of Fireplace
Opening
Figure 6 -
Mantel Clearances
Stud
Header
X
Y
B
Z
C
D
noTe: CDVR33SC7 has no standoffs.
CDV42/47
Ref.
CDV33
8" (03 mm) 8" (03 mm)
FP2285b
mantel clearances
6" (15 mm) 6" (15 mm)
6" (15 mm)
Z
Z\x" (64 mm) Z\x" (64 mm)
Stud
Header
2 "
(64 mm)
12"
(305 mm)
Stud
FP2285 36
mantel clearances
1"
1 "
3 "
2 "
3"
5"
6"
Front View
FP2286
Mantel leg clear
Standoff
FP85b
CDV42/47
Standoff
FP85
Wall
Combustible
Material Area
4 "
45°
11