28 | Condensate Drain

1. Remove and discard factory provided screws
from locations where hanging brackets will be
installed shown in Figure #93
Figure # 93
2. Mount 5 brackets to unit corner post using the
Bolts provided in the kit as shown on Figure # 94
WARNING: Do not re-use screws removed
from the unit on step 1 to mount the
hanging brackets to the unit.
Figure # 94
WARNING: Follow all applicable codes and
requirements when hanging this unit,
selecting threaded rod material, etc.
3. Install rubber grommet onto the brackets as
shown in Figure # 95
4. Hang the unit and assemble the field provided
Thread rod, nuts and washers on to the brackets as
shown in Figure # 95
6 720 220 406 (2015/02)
WARNING:Rods must be securely anchored
to the ceiling
CONDENSATE DRAIN
A drain line must be connected to the heat pump
and pitched away from the unit a minimum of 1/8"
per foot to allow the condensate to flow away from
the unit.
When converting unit from left-hand return to
right-hand return, condensate drain connection
must be relocated. Refer to Pg#20.
This connection must be in conformance with local
plumbing codes. A trap must be installed in the
condensate line to insure free condensate flow.
HZ Heat Pump Drain Pan is not internally
sloped.
Subject to change without prior notice
SM Series Heat Pump