OWNERS / TECHNICAL MANUAL
This UPS does not include a Bypass Input circuit breaker (MCCB). The
Bypass Input contactor (CB3) does not protect against load induced
short circuits. The bypass input circuit breaker (MCCB) is field supplied
and installed. Breaker(MCCB)'s Specifications are as follows:
Capacity (kVA) Bypass Voltage (VAC) Maximum Bypass
100
100
100
150
150
150
225
225
225
300
300
375
375
MITSUBISHI ELECTRIC 9700SERIES UPS
9700 SERIES UPS
WARNING 2
Rating (AAC)
208
278
480
120
600
96
208
416
480
180
600
144
208
625
480
271
600
217
480
361
600
289
480
451
600
361
Page Number:
v
Recommended
Breaker (A)
350
150
100
500
225
150
700
300
225
400
300
500
400