3. SIGNALS AND WIRING
3.11 Servo amplifier connectors (CNP1, CNP2) wiring method (When MR-ECPN1-B and MR-ECPN2-B of
an option are used.)
(1) Termination of the cables
Solid wire: After the sheath has been stripped, the cable can be used as it is. (Cable size: 0.2 to
2.5mm
)
2
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to
avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder
the core as it may cause a contact fault. (Cable size: 0.2 to 2.5mm
terminal may be used to put the wires together.(Phoenix contact make)
Cable size
[mm
1.25
1.5
2
2.5
2
]
AWG
For 1 cable
BT1.25-9-1
16
TUB-1.25
16
AI1.5-8BK
BT2-9-1
14
TUB-2
AI2.5-8BU
14
AI2.5-8BK-1000
8 to 9 mm
Bar terminal type
For 2 cables
AI-TWIN2
1.5-8BK
AI-TWIN2
1.5-12BK
AI-TWIN2
2.5-10BU
AI-TWIN2
2.5-13BU
3 - 45
)Alternatively, a bar
2
Crimping tool
NH1
NICHIFU
YHT-2210
JST
CRIMPFOX-UD6
Phoenix Contact
NH1
NICHIFU
YHT-2210
JST
CRIMPFOX-UD6
Phoenix Contact
Maker